Product Description
Industrial & Manufacturing Applications:
- Plastics Processing : Injection molding, blow molding, extrusion
- Thermoform Machines Temperature control for plastic sheet forming
- Coating Systems : Regulating temperature for uniform coatings
- Surface Processing : Electroplating, anodizing, and metal finishing
- Welding Engineering : Cooling for welding torches and laser welding
- Machine Tools : Spindle cooling, cutting fluid cooling
Energy & Environmental Applications:
- Biogas & Natural Gas Treatment : Cooling for gas purification systems
- Compressed Air Treatment : Removing moisture in air compression systems
- HVAC & Building Cooling : Climate control for commercial buildings
Medical & Pharmaceutical Applications
- Chemical & Pharmaceutical Processes : Temperature-sensitive reactions
- Medical Imaging Systems : MRI, CT scan cooling
- Laser Technology : Cooling for medical and industrial laser systems
Printing & Packaging Applications:
- Flexographic Printing Systems : Ink cooling for high-speed printing
- Offset Printing Machines: Maintaining ink viscosity and press stability
Advanced Technology & Electronics
- Semiconductor & PCB Manufacturing: Cooling electronic components
- Data Centers & Server Cooling : Preventing overheating of IT infrastructure
Food & Beverage Industry Applications:
- Food & Beverage Processing: Dairy, breweries, beverage filling lines
- Cold Storage & Refrigeration : Chilling storage rooms and transport
Automotive & Aerospace Applications:
- Battery Cooling for EVs : Managing temperature in electric vehicle batteries
- Aerospace Component Manufacturing : Temperature control in precision machining
Model FM
|
|
002-W
|
003-W
|
005-W
|
007-W
|
010-W
|
014-W
|
020-W
|
024-W
|
Cooling capacity
|
kw
|
1.7
|
3.3
|
5.2
|
7.8
|
10.8
|
14.6
|
20.3
|
23.6
|
Compressor abs. Power
|
kw
|
0.7
|
1.3
|
1.4
|
1.7
|
2.5
|
3.2
|
4.4
|
5.4
|
Power supply
|
v/oh. / Hz
|
230/1/50
|
400/3/50
|
Protection index
|
|
33
|
54
|
Refrigerant
|
|
R407c
|
Compressor
|
Type
|
|
Hermetic pistons
|
scroll
|
Compressor/ circuit
|
|
1/1
|
Max abs. Power compressor
|
kw
|
0.7
|
1.3
|
1.5
|
2.4
|
3.8
|
4.4
|
5.7
|
6.6
|
Axial fans
|
Quantity
|
N. deg
|
1
|
1
|
1
|
1
|
1
|
1
|
2
|
2
|
Max. abs. Power fan
|
kw
|
0.07
|
0.12
|
0.12
|
0.3
|
0.3
|
0.4
|
0.4
|
0.4
|
Air flow
|
m3/h
|
430
|
1295
|
1295
|
3437
|
3437
|
4337
|
6878
|
6159
|
Water cooled version
|
Condenser water flow
|
m3/h
|
N.A
|
1.5
|
2.1
|
2.5
|
Condenser connections
|
In
|
N.A
|
3/4"
|
3/4"
|
3/4"
|
Pump P30
|
Max. abs. power
|
kw
|
0.4
|
0.4
|
0.4
|
0.9
|
0.9
|
1.0
|
1.3
|
1.3
|
Water flow (nom/ max)
|
m3/h
|
0.3/ 1.9
|
0.6/ 1.9
|
0.9/ 1.9
|
1.3/ 4.8
|
1.6/ 4.8
|
2.5/ 6
|
3.4/ 9.6
|
4.9/ 9.6
|
Head pressure (nom/ max)
|
m H2O
|
35/5
|
35/5
|
26/5
|
30/12.8
|
29/12.8
|
29/21
|
29/17.3
|
28/17.3
|
Dimension and weight
|
Width
|
mm
|
520
|
755
|
755
|
756
|
756
|
756
|
756
|
756
|
Depth
|
mm
|
500
|
535
|
535
|
806
|
806
|
806
|
1206
|
1206
|
Height
|
mm
|
550
|
801
|
801
|
1405
|
1405
|
1405
|
1405
|
1405
|
Connection in/out
|
In
|
1/2"
|
3/4"
|
3/4"
|
3/4"
|
3/4"
|
3/4"
|
1"
|
1"
|
Tank capacity
|
I
|
15
|
15
|
22.5
|
65
|
65
|
65
|
100
|
100
|
Weight (axial)
|
kg
|
40
|
80
|
85
|
160
|
165
|
175
|
220
|
230
|
Weight (water cooled)
|
kg
|
n/a
|
n/a
|
n/a
|
n/a
|
n/a
|
175
|
220
|
230
|
Noise level
|
Sound pressure (axial)
|
dB(A)
|
52
|
52
|
52
|
53
|
53
|
50
|
50
|
50
|
At water in/out temperature 20/15 deg C, glycol 0 %, either 25 deg C ambient temperature (air-cooled models) or 25 deg C condenser water inlet temperature with 35 deg C condensing temperature (water-cooled models)
Referred to axial fan version in free feld conditions at a distance of 10 m from until, measured on condenser side, 1 m from ground
Accessories
- Water fill kits: non-ferrous pressurized, automatic or ambient manual kits, for water filling in any installation
- Remote control kits: base version for remote ON/OFF and general alarm monitoring. Advanced version for complete reunit monitoring.
- Wheels (ICEP002- ICEP014): for ease of transport
- Water filters: for circuit cleanliness and machinery protection.
- Water by-pass: non-ferrous, externally adjustable allowing the correct flow through the system to be set
- Control panel cover: from ICEP007,can be supplied already installed.